Product Description
The Fronius Symo Commercial Inverter is designed to deliver dependable performance for commercial solar applications. Offering power categories from 10 to 24 kW, the Fronius Symo Commercial Inverter ensures high flexibility with its wide input voltage range and dual MPP trackers. Easy internet connectivity via WLAN or Ethernet makes the Fronius Symo Commercial Inverter one of the most advanced and communicative devices available. With safety features like a built-in arc detector and robust design, the Fronius Symo Commercial Inverter is the ideal choice for businesses seeking efficiency, reliability, and long-term energy savings.
Technical Data
| Input Data | |
|---|---|
| Number of MPP trackers | 1 |
| Recommended PV Power (kWp) | 12,0 - 19,5 kWp |
| Max. usable input current | 50 A |
| Max. usable input current total (MPPT1 + MPPT2) | 50 A |
| Max. array short circuit current (1.5 * Imax) | 75 A |
| Nominal input voltage | 325 V |
| DC input voltage range (Udc min - Udc max) | 325 - 1000 V |
| MPP Voltage Range | 325 - 850 V |
| Max. input voltage (Udc max) | 1000 V |
| Integrated DC string fuse holders | 6- and 6+ |
| Output Data | |
| Max. output power 480 V | NA |
| Max. output power 240 V | NA |
| Max. output power 208 V | 15 kVA |
| Output configuration | 3~ NPE 208/220 V |
| Frequency range | 45 - 65 Hz |
| Frequency | 60 Hz |
| Power factor range | 0 - 1 ind./cap. |
| Max continuous output current 480 V | NA |
| Max. continuous output current 240 V | NA |
| Max. continuous output current 208 V | 41,6 A |
| OCPD/AC breaker size 480 V | NA |
| OCPD/AC breaker size 208 V | 60 A |
| Max. efficiency | 97,3 % |
| CEC efficiency 480 V | NA |
| CEC efficiency 240 V | NA |
| CEC efficiency 208 V | 96,5 % |
| General Data | |
| UL safety standards & network regulations | UL 1741-2015, UL 1998, UL 1699B Issue 2-2013 |
| Dimension / width | 511 mm |
| Dimension / height | 724 mm |
| Dimension / depth | 226 mm |
| Weight | 35,52 kg |
| Degree of protection | NEMA 4X |
| Night-time consumption | < 1 W |
| Inverter design | Transformerless |
| Cooling | Variable speed fan |
| Ambient Temperature Range | -40°C - +60°C |
| Maximum Relative Humidity | 0 - 100 % |
| Max. altitude | 2000 m (6560 ft) with a max. input voltage of 1000 V / 3400 m (11160 ft) with a max. input voltage of 850 V |
| Certificates and compliance with standards | UL 1741-2010, UL1998 (for functions: AFCI and isolation monitoring), IEEE 1547-2003, IEEE 1547.1-2008, ANSI/IEEE C62.41, FCC Part 15 A & B, NEC Article 690, C22. 2 No. 107.1-01 ( September 2001), UL1699B Issue 2 -2013, CSA TIL M-07 Issue 1 -2013 |
| DC connection technology | 6x DC+ and 6x DC- screw terminals for copper (solid / stranded / fine stranded) or aluminium (solid / stranded) |
| AC connection technology | Screw terminals 14-6 AWG |
| Interference emission class | B |
| Protection Devices | |
| DC reverse polarity protection | Yes |
| Anti islanding | Internal in accordance with UL 1741-2005, IEEE 1547-2003 and NEC |
| Over temperature protection | Output power derating / Active cooling |
| AFCI | Yes |
| Rapid shutdown compliant | Yes (according to NEC 2014) |
| Ground fault protection with isolation monitor interrupter | Yes |
| DC disconnector | Yes |
| Interfaces | |
| USB (type A socket) | Datalogging and inverter update possible via USB |
| 2x RS422 (RJ45 socket) | Fronius Solar Net |
| Wi-Fi / Ethernet / Serial / Datalogger and webserver | Wireless standard 802.1 1 b/g/n / Fronius Solar.web, SunSpec Modbus TCP, JSON / SunSpec Modbus RTU - Available with the Fronius Datamanager 2.0 Card only |
| 6 inputs and 4 digital I/Os | Load management signaling, multipurpose I/O - Available with the Fronius Datamanager 2.0 Card only |