Specifications
- Model Number: HSS120V3LS.
- Nominal Cooling Capacity: 10 Tons (120 000 Btu/hr).
- Outdoor Operating Temperature range: -30⁰C (-22⁰F) to +45⁰C (113⁰F)
- Power Supply: 220-240V / 1 Ph / 60Hz.
- Noise Level: 63 dBa.
- Full Load Amp (FLA): 62.5 A.
- MCA / MOP: 96 / 130 A.
- Nominal Heat Transfer Fluid Flow (US GPM): 28 (Water).
- Water Friction Loss at Nominal Flow (ft W.G.): 13.382.
- Water Inlet/Outlet Diameter: 2″ (DN50).
- Chilled Water Supply Temperature: Nominal 7⁰C (44.6⁰F), Minimum 5⁰C (41⁰F). Maximum 12⁰C (53.6⁰F).
- Hot Water Supply Temperature: Minimum 35⁰C (95⁰F), Maximum 60⁰C (140⁰F).
- Heat Pump is equiped with outdoor temperature reset feature.
- Controller uses Modbus Protocol (Table points is available upon).
- DC Inverter Panasonic Compressor with Enhanced Vapor Injection.
- Uses R32 Refrigerant.
- Certification: CSA C22.2 No. 236-15 and UL 1995:2015 R8.18.
Typcial ATW HP Installation