Specifications
- Model Number: HSS030V2LM.
- Nominal Cooling Capacity: 2.5 Tons (30 000 Btu/hr).
- Outdoor Operating Temperature range: -25⁰C (-13⁰F) to +45⁰C (113⁰F)
- Power Supply: 220-240V / 1 Ph / 60Hz.
- Noise Level: 52 dBa.
- Full Load Amp (FLA): 16.23 A.
- MCA / MOP: 29.41/ 36.56 A.
- Nominal Heat Transfer Fluid Flow (US GPM): 8.2 (Water) / 9.7 (50%
- Propylene Glycol).
- Water Friction Loss at Nominal Flow (ft W.G.): 9.03.
- Water Inlet/Outlet Diameter: 1″ (DN25).
- Chilled Water Supply Temperature: Nominal 7⁰C (44.6⁰F), Minimum 5⁰C (41⁰F). Maximum 12⁰C (53.6⁰F).
- Hot Water Supply Temperature: Minimum 35⁰C (95⁰F), Maximum 60⁰C (140⁰F).
- Heat Pump is equiped with outdoor temperature reset feature.
- Carel Controller uses Modbus Protocol (BMS interface cards are available upon request).
- DC Inverter Panasonic Compressor with Enhanced Vapor Injection.
- Uses R410a Refrigerant.
- Certification: CSA C22.2 No. 236-15 and UL 1995:2015 R8.18
Typcial ATW HP Installation
Control and Wiring Interface
Heat Pump has an outdoor temperature sensor and it can be programmed to swtich between cooling and heating automatically based on outdoor temperature. It has also the possibility to be managed by a third party controller: It can be turned ON/OFF via port 7-8, Switched to Cooling via port 7-9 and switched to Heating via port 7-10.
Heating/Cooling Performance
Heating Performance
Cooling Performance








Reviews